Table 10.1: Boiler Ratings
 |
Peerless Pinnacle |
 |
Shipping Weight, lb |
| Model Number |
Input, MBH |
Gross Output, MBH |
Net I=B=R Ratings Water1,2, MBH |
Thermal Efficiency, % |
Combustion Efficiency, % |
| Min |
Max |
| PI-399 |
100 |
399 |
379 |
330 |
93.4 |
95.1 |
252 |
1. Net I=B=R ratings are based on an allowance of 1.15.
2. Consult factory before selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
Table 10.2: Combustion Air Fan Speed
| BoilerModel |
Fan Speed - RPM |
| High Fire |
Ignition |
Low Fire |
| PI-399 |
7700 |
3000 |
1900 |
Note: These values are subject to change without notice.
Don't see the information you need? See the "Related Documents" tab for product resource downloads.