Series 211A* |
 |
Boiler H.P. |
Water Content |
| Model Number |
Input, MBH |
Gross Output, MBH |
Net I=B=R Ratings3 |
Thermal Efficiency, % |
Combustion Efficiency4, % |
| Steam, sqft |
Steam2, MBH |
Water1, MBH |
Water, gal |
Steam, gal |
| 211A-04 |
630 |
504 |
1575 |
378 |
438 |
76.9 |
80.0 |
15.1 |
44.12 |
31.64 |
| 211A-05 |
840 |
672 |
2100 |
504 |
584 |
77.4 |
80.0 |
20.1 |
55.15 |
39.55 |
| 211A-06 |
1050 |
840 |
2625 |
630 |
730 |
77.7 |
80.0 |
25.1 |
66.18 |
47.46 |
| 211A-07 |
1260 |
1008 |
3150 |
756 |
877 |
77.8 |
80.0 |
30.1 |
77.21 |
55.37 |
| 211A-08 |
1470 |
1176 |
3675 |
882 |
1023 |
77.9 |
80.0 |
35.1 |
88.24 |
63.28 |
| 211A-09 |
1680 |
1344 |
4229 |
1015 |
1169 |
78.0 |
80.0 |
40.1 |
99.27 |
71.19 |
| 211A-10 |
1890 |
1512 |
4808 |
1154 |
1315 |
78.1 |
80.0 |
45.2 |
110.3 |
79.10 |
| 211A-11 |
2100 |
1680 |
5392 |
1294 |
1461 |
78.2 |
80.0 |
50.2 |
121.33 |
87.01 |
| 211A-12 |
2310 |
1848 |
5971 |
1433 |
1607 |
78.2 |
80.0 |
55.2 |
132.36 |
94.92 |
| 211A-13 |
2520 |
2016 |
6521 |
1565 |
1753 |
77.7 |
80.0 |
60.2 |
143.39 |
102.83 |
| 211A-14 |
2730 |
2184 |
7067 |
1696 |
1899 |
77.8 |
80.0 |
65.2 |
154.42 |
110.74 |
| 211A-15 |
2940 |
2352 |
7608 |
1826 |
2045 |
77.9 |
80.0 |
70.3 |
165.45 |
118.65 |
| 211A-16 |
3150 |
2520 |
8154 |
1957 |
2191 |
77.9 |
80.0 |
75.3 |
176.48 |
126.56 |
| 211A-17 |
3360 |
2688 |
8696 |
2087 |
2337 |
78.0 |
80.0 |
80.3 |
187.51 |
134.47 |
| 211A-18 |
3570 |
2856 |
9238 |
2217 |
2483 |
78.0 |
80.0 |
85.3 |
198.54 |
142.38 |
| 211A-19 |
3780 |
3024 |
9783 |
1348 |
2630 |
78.1 |
80.0 |
90.3 |
209.57 |
150.29 |
| 211A-20 |
3990 |
3192 |
10,325 |
2478 |
2776 |
78.1 |
80.0 |
95.4 |
220.6 |
158.2 |
| 211A-21 |
4200 |
3360 |
10,871 |
2609 |
2922 |
78.1 |
80.0 |
100.4 |
231.63 |
166.11 |
| 211A-22 |
4410 |
3528 |
11,413 |
2739 |
3068 |
78.2 |
80.0 |
105.4 |
242.66 |
174.02 |
| 211A-23 |
4620 |
3696 |
11,958 |
2870 |
3214 |
77.9 |
80.0 |
110.4 |
253.69 |
181.93 |
| 211A-24 |
4830 |
3864 |
12,500 |
3000 |
3360 |
77.9 |
80.0 |
115.4 |
264.72 |
189.84 |
Note: For LP Ratings decrease by 2.5%.
* Assembled blocks available to 19 sections only.
1 Net I=B=R water ratings based on an allowance of 1.15.
2 Net I=B=R steam ratings based on an allowance of: 04 to 08=1.333, 09(Nat)=1.324, 09(LP)=1.327, 10(Nat)=1.310, 10(LP)=1.312, 11(Nat)=1.298, 11(LP)=1.300, 12(Nat)=1.290,
12(LP)=1.291, 13 to 19=1.288.
3 Consult factory before selecting a boiler for installation having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.
4 Combustion efficiency determined in accordance with ANSI Z21.13, Gas-Fired Low-Pressure Steam and Hot Water Boilers.
5 Consult product catalog literature for detailed ratings information up to 9,450 MBH.
Don't see the information you need? See the "Related Documents" tab for product resource downloads.