Important Information Regarding Flood Damaged Heating Equipment


Residential Boilers - Oil Boilers Series EC™ Boiler

The Series EC™ is a residential, oil-fired, cast iron boiler for steam or hot water systems. The large water content of the boiler makes it ideal for steam and large volume hot water applications. The EC boiler has an AFUE of up to 87.6% – ENERGY STAR® certified – and features high efficiency, flame retention burners in choice of Beckett, Carlin or Riello. Optional tankless coils can be added for all your domestic hot water needs. A full, non-prorated lifetime warranty is included for all water boilers and a limited 10-year warranty covers the heat exchanger of steam boilers.

Federal Tax Credits for Energy Efficiency (ends 12/31/25): Hot Water Boilers (Natural Gas, Propane, Oil) Tax Credit | ENERGY STAR
Qualified Manufacturer ID – B1U7




Product Details:

Type: Residential
Construction: Cast Iron
Fuel: #2 Oil; and certified for biodiesel fuel blends up to 20% (B20)
Input: 101 to 420 MBH
Output: 84 to 347 MBH
Venting: Natural Draft
Trim: Water or Steam
Combustion: Flame Retention Burner


 

Series EC™ Water Content, Gallons Min. Stack Draft Reqd.
Model Number Input Output3,4 MBH B20 Input B20 Output MBH Net Ratings2 AFUE, % Thermal Effic.4, % Combustion Effic.,%
GPH1 MBH Water Steam MBH Water Steam Steam, sqft Steam, MBH Water, MBH
Water Steam Water Steam
EC(T)-e-03 0.75 105 93 92 101 85 84 288 69 81 87.6* 86.5 17.40 14.16 -.03
EC(T)-e-03 1.00 140 122 121 135 109 108 379 91 106 86.5 85.5 17.40 14.16 -.04
EC(T)-e-04 1.25 175 153 152 169 139 138 475 114 133 86.5 85.4 21.72 17.28 -.03
EC(T)-e-04 1.50 210 183 181 203 170 168 567 136 159 86.3 85.5 21.72 17.28 -.04
EC(T)-e-05 1.75 245 215 213 237 201 199 667 160 187 86.8 85.5 26.04 20.40 -.03
EC(T)-e-05 2.00 280 243 242 271 232 231 758 182 211 86.2 85.0 26.04 20.40 -.04
EC(T)-05 2.40 336 279 279 325 267 267 874 210 243 83.0 85.1 26.04 20.40 -.05
EC(T)-e-06 2.20 308 259 298 247 811 194 84.0 23.52 -.04
EC(T)-e-06 2.40 336 282 325 267 883 212 84.0 23.52 -.04
EC(T)-06 2.75 385 321 321 372 305 303 1006 241 279 83.3 84.4 30.36 23.52 -.04
EC(T)-06 3.00 420 347 347 406 329 329 1087 261 302 82.5 83.7 30.36 23.52 -.05

NOTE: all values are for Type #2 oil unless noted as B20.

*As an ENERGY STAR® partner, PB Heat, LLC has determined that these firing rates meet the ENERGY STAR® guidelines for energy efficiency.

† All chimneys are 8″ x 8″ x 20′ except those models denoted with †, which are 8″ x 12″ x 20′.

1 Burner input based on No. 2 fuel oil with a heating value of 140,000 Btu per gallon.

2 Net water ratings based on an allowance of 1.15, net steam ratings based on an allowance of 1.333. Consult factory before selecting a boiler for installations having unusual piping and pickup requirements, such as intermittent system operation, extensive piping systems, etc.

3 Output is Heating Capacity for models with inputs <300 MBH and Gross Output for models with inputs ≥300 MBH. Heating Capacity and Annual Fuel Utilization Efficiency (AFUE) ratings are based on U.S. Government tests.

4 Thermal efficiency and gross output are determined in accordance with ANSI/AHRI Standard 1500.






Series EC™ Boiler Dimensions

Boiler Model Number Jacket Depth
“A”
Jacket Width
“B”
Jacket Height
“C”
Rear of Jacket to c/l of Vent
“D”
Distance Between Supply Tappings
“E”
Vent Size Diameter
“F”
EC(T)-e-03 15-3/4″ 22-1/2″ 42″ 8-3/4″ 9-1/16″ 6″
EC(T)-e-04 19-15/16″ 22-1/2″ 42″ 10-7/8″ 13-1/4″ 7″
EC(T)-e-05 24-1/8″ 22-1/2″ 42″ 13″ 17-7/16″ 8″
EC(T)-e-06/06 28-5/16″ 22-1/2″ 42″ 15-1/16″ 21-5/8″ 9″